Thursday, June 7, 2012

Dielectric strength of transformer oil test equipment power

Application:
Oil tester fully automatic IIJ series has been designed in accordance with the requirements of test method IEC156 strength of insulating oil via the appropriate programming, boost automatic, while stirring, and has a function of step-down, and display print out. After the destruction of the oil medium, HV break off, to enable the automatic separation of the control system partially, but works within 10 seconds, the safety of the equipment, security and personnel protection this effectively secure. Tester is suitable for testing the dielectric strength of oil medium, has been the same way as Insulating Oil Testers
Can withstand voltage of transformer oil for testing.

Features:
MCU I / O pins new, fully automated control 1) use.
Test the time of stirring 2), the number of idling time is set via a digital set.
3) Results test is displayed, printed out automatically.
It provides powerful features 4) anti-interference.
High-precision 5) of high capacity testing and anti-jamming.
Easy to operate 6) operation, small size, light weight and convenient in the open air very convenient for maintenance
7) is useful for reading and printing, you can store 99 groups oil testing data. Test data, you can keep 100 years with the power turned off.
8 hours) system is the system time just for reference (you can go on running under power off, it is to base the timing is not possible.) H V Testing Set

Technology and parameter data
A. Power Supply: AC22 0V 10%, 50 HZ
Two. Output voltage: 60 KV, 80KV, 100KV
Three. Capacity: 1.6KVA, 2.0KVA
Four. Pressure rise rate: 2 KVA / S about
Five. 3% rate pressure test
6. To break the sensitivity: <2KV
Seven. Waveform distortion: ≤ 3%
Eight. Of ≤ 10ms: Time breakdown
Nine. 0 ℃ -40 ℃, Humidity: Temperature: operating environment for most humidity85% relative
10. -20 ℃ -40 ℃, Humidity: Temperature: humidity75% relative for most storage environments.
11. Operational height: <150 meters (the height is 1,500 meters or more if it is, it can be specially designed)
12. Test cell: glass, volume 300-500 ml, protective cover, and the mixture was stirred.
13. Electrode: the radius of the hemisphere 25mm / 36 mm diameter spherical stainless steel, as a gap of 2.5 mm Very Low Frequency AC Hipots
Per IEC-156.
14. Nitial time of sample oil stand: 180 seconds
Intermediate stand time of the oil sample: 60 seconds
String time of sample oil: 60 seconds
6: The number of consecutive test
15. Total of approximately 55kg: weight for high voltage and control

No comments: